Unlike other cables, fire resistant cables should work even when instantly uncovered to the hearth to keep important Life Safety and Fire Fighting equipment working: Fire alarms, Emergency Lighting, Emergency Communication, Fire Sprinkler pumps, Fireman’s Lift sub-main, Smoke extraction fans, Smoke dampers, Stair pressurization followers, Emergency Generator circuits etc.
In order to classify electric cables as fire resistant they’re required to endure testing and certification. Perhaps the first frequent hearth exams on cables had been IEC 331: 1970 and later BS6387:1983 which adopted a gas ribbon burner test to produce a flame in which cables have been positioned.
Since the revision of BS6387 in 1994 there have been 11 enhancements, revisions or new test requirements introduced by British Standards for use and software of Fire Resistant cables however none of these appear to address the core concern that fire resistant cables where examined to common British and IEC flame take a look at standards aren’t required to carry out to the identical fireplace performance time-temperature profiles as each other construction, system or component in a building. Specifically, the place fireplace resistant structures, methods, partitions, fire doors, hearth penetrations fire obstacles, flooring, walls etc. are required to be fire rated by building laws, they are tested to the Standard Time Temperature protocol of BS476 components 20 to 23 (also known as ISO834-1, ASNZS1530pt4, EN1363-1 and in America and Canada ASTM E119-75).
These exams are conducted in giant furnaces to duplicate real submit flashover fireplace environments. Interestingly, Fire Resistant cable take a look at standards like BS 6387CWZ, SS299, IEC 60331 BS8343-1 and a pair of, BS8491 only require cables to be exposed to a flame in air and to lower ultimate take a look at temperatures (than required by BS476 pts 20 to 23). Given Fire Resistant cables are prone to be uncovered in the same fireplace, and are wanted to ensure all Life Safety and Fire Fighting systems stay operational, this reality is perhaps shocking.
Contrastingly in pressure gauge หลักการ ทํา งาน , Belgium, Australia, New Zealand, USA and Canada Fire Resistant cable systems are required to be tested to the same fireplace Time Temperature protocol as all other building parts and this is the Standard Time Temperature protocol to BS476pts 20-23, IS0 834-1, EN1363-1 or ASTM E119-75 in USA.
The committees growing the usual drew on the steerage given from the International Fire Prevention Congress held in London in July 1903 and the measurements of furnace temperatures made in plenty of hearth checks carried out in the UK, Germany and the United States. The checks were described in a series of “Red Books” issued by the British Fire Prevention Committee after 1903 in addition to these from the German Royal Technical Research Laboratory. The finalization of the ASTM normal was closely influenced by Professor I.H. Woolson, a Consulting Engineer of the USA National Board of Fire Underwriters and Chairman of the NFPA committee in Fire Resistive Construction who had carried out many tests at Columbia University and Underwriters Laboratories in Chicago. The small time temperature variations between the International ISO 834-1 check as we all know it right now and the America ASTM E119 / NFPA 251 exams likely stemmed from this time.
Image courtesy of MICC Ltd.
The curve as we see it right now (see graph above) has turn into the standard scale for measurement of fireside test severity and has proved relevant for many above floor cellulosic buildings. When components, constructions, elements or systems are tested, the furnace temperatures are managed to conform to the curve with a set allowable variance and consideration for initial ambient temperatures. The requirements require components to be examined in full scale and beneath circumstances of assist and loading as outlined to find a way to characterize as precisely as potential its features in service.
This Standard Time Temperature testing protocol (see graph right) is adopted by nearly all nations around the world for hearth testing and certification of just about all building constructions, components, systems and parts with the interesting exception of fireside resistant cables (exception in USA, Canada, Australia, Germany, Belgium and New Zealand the place fireplace resistant cable methods are required to be examined and permitted to the Standard Time Temperature protocol, identical to all other building buildings, parts and components).
It is necessary to grasp that application requirements from BS, IEC, ASNZS, DIN, UL and so forth. where fire resistive cables are specified for use, are only ‘minimum’ necessities. We know at present that fires are not all the same and research by Universities, Institutions and Authorities around the world have identified that Underground and some Industrial environments can exhibit very different hearth profiles to these in above ground cellulosic buildings. Specifically in confined underground public areas like Road and Rail Tunnels, Underground Shopping centers, Car Parks fireplace temperatures can exhibit a really quick rise time and may attain temperatures well above these in above ground buildings and in far much less time. In USA right now electrical wiring methods are required by NFPA 502 (Road Tunnels, Bridges and other Limited Access Highways) to withstand hearth temperatures as much as 1,350 Degrees C for 60 minutes and UK British Standard BS8519:2010 clearly identifies underground public areas corresponding to automotive parks as “Areas of Special Risk” the place extra stringent test protocols for essential electric cable circuits could have to be considered by designers.
Standard Time Temperature curves (Europe and America) plotted in opposition to frequent BS and IEC cable tests.
Of course all underground environments whether road, rail and pedestrian tunnels, or underground public environments like purchasing precincts, automobile parks and so on. could exhibit completely different fire profiles to these in above ground buildings because In these environments the warmth generated by any hearth can not escape as easily as it’d in above floor buildings thus relying extra on heat and smoke extraction equipment.
For Metros Road and Rail Tunnels, Hospitals, Health care services, Underground public environments like buying precincts, Very High Rise, Theaters, Public Halls, Government buildings, Airports and so on. this is particularly essential. Evacuation of those public environments is usually gradual even during emergencies, and it’s our duty to ensure everyone seems to be given the very best chance of secure egress throughout fire emergencies.
It can also be understood at present that copper Fire Resistant cables where installed in galvanized metal conduit can fail prematurely throughout hearth emergency because of a response between the copper conductors and zinc galvanizing contained in the steel conduit. In 2012 United Laboratories (UL®) in America eliminated all certification for Fire Resistive cables where put in in galvanized steel conduit for that reason:
UL® Quote: “A concern was brought to our attention related to the efficiency of those products in the presence of zinc. We validated this finding. As a results of this, we changed our Guide Information to indicate that every one conduit and conduit fittings that are available in contact with fire resistive cables ought to have an inside coating freed from zinc”.
Time temperature profile of tunnel fires utilizing automobiles, HGV trailers with completely different cargo and rail carriages. Graph extract: Haukur Ingason and Anders Lonnermark of the Swedish National Testing and Research Institute who introduced the paper on the First International Symposium in Prague 2004: Safe and Reliable Tunnels.
It would appear that some Standards authorities all over the world may have to review the current test methodology currently adopted for fireplace resistive cable testing and perhaps align the efficiency of Life Safety and Fire Fighting wiring methods with that of all the opposite fireplace resistant constructions, components and techniques in order that Architects, constructing designers and engineers know that once they need a hearth ranking that the important wiring system will be equally rated.
For many energy, control, communication and knowledge circuits there might be one expertise available which may meet and surpass all current fireplace exams and functions. It is a solution which is regularly used in demanding public buildings and has been employed reliably for over eighty years. MICC cable expertise can provide a complete and full reply to all the issues associated with the hearth safety dangers of recent flexible organic polymer cables.
The metallic jacket, magnesium oxide insulation and conductors of MICC cables ensure the cable is effectively fire proof. Bare MICC cables have no organic content so merely can’t propagate flame or generate any smoke. The zero fuel-load of those MICC cables ensures no heat is added to the hearth and no oxygen is consumed. Being inorganic these MICC cables can not generate any halogen or toxic gasses at all together with Carbon Monoxide. MICC cable designs can meet all of the present and constructing fireplace resistance efficiency standards in all international locations and are seeing a significant improve in use globally.
Many engineers have beforehand considered MICC cable technology to be “old school’ however with the brand new research in fire efficiency MICC cable system are actually confirmed to have far superior fire performances than any of the newer extra trendy versatile hearth resistant cables.